SMART 3G C2-LD
Sensitron / Gas detection

SMART 3G C2-LD

Industrial gas detector family for ATEX Zone 1 applications, with a high-visibility LED crown and sensor-dependent gas ranges. Dust-area use requires the specified optional adapter.

Technical documents ↓
ManufacturerSensitron
Model / familySMART 3G C2-LD
SystemGas detection
Selection & quotationBased on project specification, configuration and quantities.

Technical specifications

Operating voltage12-24 VdcSource · 2 ↗
IP ratingIP65Source · 3 ↗
Dimensions145 x 187 x 108 mmSource · 3 ↗
Weight1900 gSource · 3 ↗
Application — CatalyticIndustrial area, ATEX Zone 1 and Zone 21 (when equipped with dust adapter, optional)Source · 2 ↗
Application — ElectrochemicalIndustrial area, ATEX Zone 1 and Zone 21 (when equipped with dust adapter, optional)Source · 2 ↗
Application — InfraredIndustrial area, ATEX Zone 1 and Zone 21 (when equipped with dust adapter, optional)Source · 2 ↗
Application — PIDIndustrial area, ATEX Zone 1 e Zone 21 (when equipped with dust adapter, optional)Source · 2 ↗
Detection principle — CatalyticCatalyticSource · 2 ↗
Detection principle — ElectrochemicalElectrochemical cellSource · 2 ↗
Detection principle — InfraredInfraredSource · 2 ↗
Detection principle — PIDPhotoionizator (PID)Source · 2 ↗
Detectable gases — CatalyticFlammable gasSource · 2 ↗
Detectable gases — ElectrochemicalO2 [0-25% Vol], CO [0-500/1000 ppm], NH3 [0-100/200/1000/5000 ppm], H2S [0- 50/100 ppm], NO [0 - 100 ppm]; H2 [0 - 2000/3000 ppm]Source · 2 ↗
Detectable gases — InfraredFlammable, refrigerant and CO2Source · 2 ↗
Detectable gases — PIDVolatile Organic Compounds (VOC) having photoionization potential up to 10.6 eVSource · 2 ↗
Measurement range — Catalytic0 - 100% LFLSource · 2 ↗
Measurement range — Infrared0 - 100% LFL flammable gas 0 - 2000 ppm refrigerant gas 0-2%Vol; 0-5%Vol; 0-30%Vol; 0-100%Vol CO2Source · 2 ↗
Measurement range — PID0 - 20 ppm (Isobutylene) 0 - 200 ppm (Isobutylene) 0 - 2000 ppm (Isobutylene)Source · 2 ↗
Outputs — CatalyticAnalogue 4-20 mA output; 3 relay board; serial RS485 output (optional)Source · 2 ↗
Outputs — ElectrochemicalAnalogue 4-20 mA output; 1 or 3 relay board (optional); serial RS485 output (optional)Source · 2 ↗
Outputs — InfraredAnalogue 4-20 mA output; 3 relay board; serial RS485 output (optional)Source · 2 ↗
Outputs — PIDAnalogue 4-20 mA output; 1 or 3 relay board (optional); serial RS485 output (optional)Source · 3 ↗
Maximum power consumption5.4 WSource · 2 ↗
Relay contact ratings — Catalytic1.0 A at 24 VdcSource · 2 ↗
Relay contact ratings — Electrochemical1.0 A at 24 VdcSource · 2 ↗
Relay contact ratings — Infrared1.0 A at 24 VdcSource · 2 ↗
Display and indicationMulti-colour LED light ringSource · 2 ↗
Housing materialEnclosure: aluminium pressure die-casting with epoxy paint chromating and chemically resistant Sensor head: stainless steelSource · 3 ↗
Storage temperature — Catalytic-40 / +85°CSource · 3 ↗
Storage temperature — Electrochemical0 / +20°C up to 6 monthsSource · 3 ↗
Storage temperature — Infrared-40 / +85°CSource · 3 ↗
Operating temperature — Catalytic-40 / +60°C *Source · 3 ↗
Operating temperature — Electrochemical-30 / +55°CSource · 3 ↗
Operating temperature — Infrared-40 / +60°C *Source · 3 ↗
Relative humidity — Catalytic20 / 90% RH @40°C *Source · 3 ↗
Relative humidity — Electrochemical15 / 90% RH non condensingSource · 3 ↗
Relative humidity — Infrared20 / 90% RH @40°C *Source · 3 ↗
Relative humidity — PID(non condensing)Source · 3 ↗

Documented system connections

Related products identified in manufacturer documentation. Check the model and configuration scope in the reference.

Ratings, approvals and compatibility apply only to the models and configurations identified in the manufacturer’s documents.